Wednesday, 12 March 2008
Quin Q-Drive Serial Connections
Port A
Use for configuring servonet address. Use a male to female serial lead with the following configuration
2-2
3-3
5-5
6-8
8-6
RS232 Port
Use for configuring drive using Q-Drive manager. Use a standard serial lead with
2-3
3-2
5-5
6-8
8-6
Saturday, 1 March 2008
Siemens Micromaster F070 Profibus Fault
Today I discovered something that has eluded me for the last few years, and now when I look at the manual it all becomes plainly obvious. Anyone who has programmed the control for a Siemens MM420/440 on S7 over profibus will no doubt have had the misfortune to come across the "F070" fault.
Reading the manual about this fault you get the following explanation
Having spoken to siemens tech support, I am told to check cables, terminations and other physical components.
Anyhow eventually some guy in a factory on a night shift tells a friend of mine that F70 is caused by having the "Enable Setpoint" and "Setpoint Valid" outputs off. I make a change to a bit of test code that switches these two bits on all the time and voila, problem solved.
I wonder why Siemens tech support didn't tell me to check this first.