- The stop lamp on the CPU was flashing.
- The BASP lamp on the CPU was on.
- The CPU would not go into run mode.
- Looking at the status stuff online in S6, the NINEU flag was on.
Siemens Manual Snippet OR using Switches on CPU
If you cannot be arsed to read the above snippet then do the following.
- Put CPU run/stop switch into STOP
- Hold OR switch in OR position
- Toggle run/stop switch into run position two times. So stop-run-stop-run-stop
- Release the OR switch
- Download program (if no EPROM fitted)
- Put run/stop switch into run
Anyhow, the OR was performed as shown, the CPU was switched back into run and everything was OK. I compared the online and offline programs.... identical. Sweet.